PMC-D726M Digital Multifunction Meter

SKU:
$160.00 USD

Sub-Model: PMC-D726M-5325DAE

PMC-D726M-5325DAE
PMC-D726M-5325DAE
PMC-D726M-L5325DAE

Main Documents

Description

PMC-D726M DIN72 3-Ø Digital Multifunction Meter


Device Introduction

  • PMC-D726M Digital Multifunction Meter is CET’s latest offer for the low-cost digital power/energy metering market. Housed in an industry standard DIN form factor measuring 72mmx72mmx71.8mm (LCD) or 72mmx72mmx76.8mm (LED), it is perfectly suited for industrial, commercial and utility metering applications.
  • The PMC-D726M features quality construction, true RMS multifunction measurements and a LED or LCD display. Compliance with the IEC 62053-21 Class 1 kWh Accuracy Standard, it provides optimum Price to Value ratio and is a cost effective replacement for traditional analog instrumentation, capable of displaying 3-phase measurements at once. The PMC-D726M optionally provides Split-Core CT (SCCT) support for retrofit applications, two Digital Inputs for status monitoring, two Digital Output for control, or one 0/4-20mA Analog Output for interfacing with 3rd party SCADA system. The standard SOE Log records meter events such as power-off, setup and DI status changes in 1ms resolution. With a standard RS-485 port and Modbus RTU protocol support, the PMC-D726M becomes a vital component of an intelligent, multifunction monitoring solution for any Power and Energy Management systems.

Product Highlight

  • Low-Cost Three-Phase Multifunction Meter
  • IEC62053-21 Class 1
  • DIN72 (68x68mm Cutout)
  • Backlit B&W LCD / High-contrast LED Display
  • Harmonics, Demands & TOU and Event Log
  • Modbus RTU,1xRS-485
  • Optional 2xDI, 2xDO,1xAO, 2xSS Pulse Output

Typical Application

  • Analog meter replacement
  • Industrial, Commercial and Utility panel metering
  • Substation, Factory and Building Automation
  • Sub-metering and Cost Allocation
  • Ideal for retrofitting with the SCCT option

Related Products

Related Solutions

Specification

Technical Specification

Voltage Inputs(V1,V2,V3,VN)
Standard
240 ULN/415 ULL
Range
10V to 120% Un
Starting Voltage
10V
PT Ratio
1-1,000,000 (Primary), 1-690 (Secondary)
Overload
1.2xUn continuous, 2xUn for 1 s
Burden
<0.02VA per phase
Frequency
45-65Hz
Current Inputs(I11,I12,I21,I22,I31,I32)
Standard Input
5A
Optional Input
1A
CT Ratio
1-30,000 (Primary), 1-5 (Secondary)
Optional SCCT Input
2mA (SCCTA Option for 5A SCCT)
40mA (SCCT Option for 100-800A SCCT)
Range
0.1% to 120%In
Starting Current
0.1% of In
Overload
1.2xIn continuous, 10xIn for 10s, 20xIn for 1s
Burden
<0.25VA per phase
Power Supply(L+,N-)
Standard
95-250VAC/DC,±10%,47-440Hz
Burden
<2W
Digital Inputs(DI1,DI2,DIC)
Type
Dry contact,24VDC internally wetted
Sampling
1000Hz
Hysteresis
1ms minimum
Digital Outputs(DO11,DO12,DO21,DO22)
Type
Form A Mechanical Relay
Loading
5A@250VAC or 30VDC
Analog Output (AO+,AO-)
Type
0-20 / 4-20mA
Parameter
Selectable
Loading
500 Ω maximum
Overload
24 mA maximum
Environmental Conditions
Operating Temp.
-25 °C to + 70°C
Storage Temp.
-40 °C to + 85°C
Humidity
5% to 95% non-condensing
Atmospheric Pressure
70 kPa to 106 kPa
Mechanical Characteristics
Panel Cutout
68x68 mm
Unit Dimensions
72x72x71.8 mm (LCD), 72x72x76.8 mm (LED)
IP Rating
IP52
Shipping Weight
0.802 kg
Shipping Dimensions
125x110x80 mm
Communications
Protocol
Modbus RTU
RS-485 Port
1
Features Summary
Display (Backlit)
B&W(Backlit)
Type of Measurement
ULN per Phase &Avg.
ULL per Phase&Avg.
Current per Phase &Avg.
Neutral Current (Calc.)
Frequency
kW per Phase & Total
kvar per Phase & Total
kVA per Phase& Total
PF per Phase& Total
kWh lmport/Export
kvarh Import/Export
kVAh Total
Power Quality
THD Voltage & Current
TOHD Voltage & Current
TEHD Voltage & Current
2nd-31st Harmonics
K-Factor
Voltage/Current Unbalance
Demands
Present Demands and Max.Demands for This Month & Last Month
Multi-Tariff TOU capability
One TOU Schedules Providing:
6 Seasons
10 Holidays
6 Daily Profiles, each with 6 Periods in 15-minute interval
4 Tariffs
Setpoints
6 Setpoints
Logs
SOE Log
16 entries

Accuracy

5A/1A Current Input
Parameters
Accuracy
Resolution
Voltage
±0.2% reading
0.1V
Current
±0.2% reading
0.001A
kW,kvar,kVA
±0.5% reading
0.001kx
kWh
IEC 62053-21 Class 1
0.01kWh
kvarh
IEC 62053-23 Class 2
0.01kvarh
PF
±1.0% reading
0.001
Frequency
±0.02Hz
0.01Hz
AO
±0.5% F.S.
--
Harmonics
IEC 61000-4-7 Class B
0.1%
K-Factor
IEC 61000-4-7 Class B
0.1
40mA SCCT Input
Parameters
Accuracy
Resolution
Voltage
±0.5% reading
0.1V
Current
±1% reading
0.001A
kW,kvar,kVA
±1% reading
0.001kx
kWh
IEC 62053-21 Class 1
0.01kWh
kvarh
IEC 62053-23 Class 2
0.01kvarh
PF
±1.0% reading
0.001
Frequency
±0.02Hz
0.01Hz
AO
±0.5% F.S.
--
Harmonics
IEC 61000-4-7 Class B
0.1%
K-Factor
IEC 61000-4-7 Class B
0.1
2mA SCCT Input
Parameters
Accuracy
Resolution
Voltage
±0.5% reading
0.1V
Current
±1% reading
0.001A
kW,kvar,kVA
±1.5% reading
0.001kx
kWh
IEC 62053-21 Class 2
0.01kWh
kvarh
IEC 62053-23 Class 2
0.01kvarh
PF
±1.5% reading
0.001
Frequency
±0.02Hz
0.01Hz
AO
±0.5% F.S.
--
Harmonics
IEC 61000-4-7 Class B
0.1%
K-Factor
IEC 61000-4-7 Class B
0.1

Standards of Compliance

Safety Requirements
CE LVD 2006 / 95 / EC
EN 61010-1: 2010
EN 61010-2-030: 2010
Electrical Safety in Low Voltage Distribution Systems up to 1000Vac and 1500Vdc
IEC 61557-12:2018(PMD)
Insulation

AC Voltage:
Insulation Resistance:
Impulse Voltage:
IEC 62052-11: 2003
IEC 62053-21: 2003
2kV@1 minute
>100MΩ
6kV,1.2/50µs
Electromagnetic Compatibility CE EMC Directive 2004 / 108 / EC (EN 61326: 2013)
Immunity Tests
Electrostatic Discharge
EN 61000-4-2:2009
Radiated Fields
EN 61000-4-3:2006+A1:2008+A2:2010
Fast Transients
EN 61000-4-4:2012
Surges
EN 61000-4-5:2014+A1:2017
Conducted Disturbances
EN 61000-4-6:2014
Magnetic Fields
EN 61000-4-8:2010
Voltage Dips and Interruptions
EN 61000-4-11:2004+A1:2017
Ring Waves
EN 61000-4-12:2017
Emission Tests
Limits and Methods of Measurement of Electromagnetic Disturbance Characteristics of Industrial,Scientific and Medical(ISM) Radio-Frequency Equipment
EN 55011:2016
Limits and Methods of measurement of Radio Disturbance Characteristics of Information Technology Equipment
EN 55032:2015
Limits for Harmonic Current Emissions for Equipment with Rated Current≤16A
EN 61000-3-2:2014
Limitation of Voltage Fluctuations and Flicker in Low-Voltage Supply Systems for Equipment with Rated Current≤16A
EN 61000-3-3:2013
Emission Standard for Residential, Commercial and Light-Industrial Environments
EN 61000-6-4:2007+A1:2011
Mechanical Tests
Spring Hammer Test
IEC 62052-11:2003
Vibration Test
IEC 62052-11:2003
Shock Test
IEC 62052-11:2003

Wiring Mode

Wiring Mode
3P4W
3-Phase 4-Wire (3P4W) Wye Direct Connection with 3CTs
3-Phase 4-Wire Wye Direct Connection with 2CTs
3P3W
3-Phase 3-Wire open Delta with 2PTs and 3CTs
3-Phase 3-Wire open Delta with 2PTs and 2CTs