PMC-592 Multi Circuit Power Monitor

SKU:
$4,160.00

Sub-Model: PMC-592-A5326100E

PMC-592-A5326100E
PMC-592-A5326100E
PMC-592-A5326010E

Main Documents

Description

PMC-592 Multi Circuit Power Monitor


Device Introduction

  • The PMC-592 MCPM is the ultimate solution for PDU, LVDB and Load Center applications that require multi-circuit monitoring. Housed in a compact metal enclosure, the PMC-592 is perfectly suited for applications that require high density metering.
  • The PMC-592 features quality construction with multifunction and High-Accuracy measurements, two Mains Inputs, up to 84 Branch Circuit Inputs and an optional 7” Touch-Screen HMI. The PMC-592 comes standard with two Digital Inputs for status monitoring, two Digital Outputs for control or alarming as well as two RTD Inputs for temperature measurements. The standard SOE Log records all setup changes, Setpoint alarms and DI/DO operations in 1ms resolution. With Ethernet and dual RS-485 as standard feature supporting Modbus RTU/TCP, HTTP, SMTP as well as SNMP, the PMC-592 becomes a vital component of an intelligent, multi-circuit monitoring solution

Product Highlight

  • Multi-Circuit Power Monitor
  • IEC 62053-22 Class 0.5S for Mains, IEC62053-21 Class 1 for Branches
  • 260.5x154x55.5mm
  • LED Indicators, Optional Touch Screen HMI
  • 2 Mains Inputs each with 3xV & 4xI, 84 Branch Circuits with CT-Strip Accessories
  • Harmonics, Demands, Waveform Log, Dip/Swell Log and Event Log
  • 1GB On-board Memory
  • Modbus RTU/TCP, SNMP, HTTP, SMTP, SNTP
  • 1xEthernet, 2xRS-485
  • 2xDI, 2xDO, 1xRTD

Typical Application

  • Data Center PDUs
  • Clean room LVDB (Low-Voltage Distribution Board)
  • Load Center Monitoring
  • Ring Main Unit Metering
  • Motor Control Center metering
  • Commercial & Residential LV High-Density Multi-Circuit monitoring

Related Products

Related Solutions

Specification

Technical Specification

Main Voltage Inputs(V1,V2,V3,VN)
Standard(Un)
277ULN/480ULL
Range
10% to 120% Un
PT Ratio
    Mains I/II-Primary
    Mains I/II-Secondary

1-1,000,000V
1-480V
Overload
2xUn continuous,4xUn for 1s
Burden
<0.05VA@277ULN per phase
Frequency
45-65Hz
Mains Current Inputs
I Nominal(In)
5A/1A (CT rated Input)
Range
1% to 120%
Starting Current
0.3% of In
CT Ratio
6000 max.for 5A,30000max.for 1A
Overload
1.2xIn continuous,10xIn for 1s
Burden
<0.3 VA per phase
Power Supply for Main Unit(L+,N-)
Standard
95-277VAC/DC,±10%,47-440Hz
Burden
<6W
Branch Inputs
CT Ratio
400 Maximum
Burden
<0.05VA per phase
Starting Current
0.2% Imax
Solid-Core CT Strip
    100A
    5A

In=100A,Imax=100A,Range=0.2%-100%
In=5A,Imax=10A,Range=1%-100%
Split-Core CT
    100A
    200A
    400A
    800A
    1600A

In=100A,Imax=120A,Range=5%-120%
In=200A,Imax=240A,Range=5%-120%
In=400A,Imax=480A,Range=5%-120%
In=800A,Imax=960A,Range=5%-120%
In=1.6kA,Imax=1.92kA,Range=5%-120%
Solid-Core CT
    400A
    800A

In=400A,Imax=480A,Range=5%-120%
In=800A,Imax=960A,Range=5%-120%
Digital Inputs(DI1,DI2,DIC)
Type
Dry contact,24VDC internally wetted
Sampling
1000Hz
Debounce
1-9999 ms programmable
Digital Outputs(DO11,DO12,DO21,DO22)
Type
Form A Mechanical Relay
Loading
5A@250VAC/30VDC
RTD Inputs(TC11,TC12,TC21,TC22)
Type
PT100
Range
-40°C-200°C
Environmental Conditions
Operating Temp.
-25 °C to + 70°C
Storage Temp.
-40 °C to + 85°C
Humidity
5% to 95% non-condensing
Atmospheric Pressure
70 kPa to 106 kPa
Pollution Degree
2
Overvoltage Category
CAT III
Mechanical Characteristics
Enclosure
Galvanized Steel
Unit Dimensions
260.5x154x55.5mm
IP Rating
IP50
Communications
Protocol
Modbus RTU,Modbus TCP,HTTP,SNMP,SNTP,SMTP
RS-485 Port(Standard)
2
Ethernet
1
Web Server
Features Summary
Display (Backlit)
Optional Color TFT 800×480 (Backlit)
Type of Measurement
ULN per Phase &Avg.
ULL per Phase&Avg.
Current per Phase &Avg.
Neutral Current (Meas.)
Frequency
kW per Phase & Total
kvar per Phase & Total
kVA per Phase& Total
PF per Phase& Total
kWh lmport/Export
kvarh Import/Export
kVAh Total
Power Quality
THD Voltage & Current
TOHD Voltage & Current
TEHD Voltage & Current
2nd-31st Harmonics
K-Factor
Voltage/Current Unbalance
Battery-backed Real-time Clock
Demands
Present Demands and Max.Demands for This Month & Last Month
Alarm Setpoints
Logs
Max./Min.Log
This month & Last Month
Interval Energy Recorder
10000 entries
Data Recorder Log
10 Data Recorders
Max. Recording Depth @ 65535 records
Waveform Recorder (WFR)
16 entries
SOE Log
1000 entries
On-board Log Memory
1GB

Accuracy

Parameters
Accuracy
Resolution
Mains Voltage
±0.2%
0.01V
Mains I1-I4
±0.2%
0.001A
kW,kVA
IEC 62053-22 Class 0.5S for Mains
IEC 62053-21 Class 1 for Branches
0.001kX
kWh,kVAh
IEC 62053-22 Class 0.5S for Mains
IEC 62053-21 Class 1 for Branches
0.1kXh
kvar,kvarh
IEC 62053-23 Class 2
0.01kvarh
0.1kvarh
PF
±1.0%
0.001
Frequency
±0.02Hz
0.01Hz
Harmonics
IEC 61000-4-7 Class B
0.01%
K-Factor
IEC 61000-4-7 Class B
0.01
RTD
±1.0°
0.1°

Standards of Compliance

Safety Requirements
LVD Directive 2014/35/EU
EN 61010-1: 2010
EN 61010-2-030: 2010
Electrical Safety in Low Voltage Distribution Systems up to 1000Vac and 1500Vdc
IEC 61557-12:2018(PMD)
Insulation
     AC Voltage
     Insulation Resistance
     Impulse Voltage

3.5kV @ 1 minute
>100MΩ
6kV+0%, 1.2/50µs
Electromagnetic Compatibility CE EMC Directive 2014/30/EU(EN 61326:2013)
Immunity Tests
Electrostatic Discharge
EN 61000-4-2:2009
Radiated Fields
EN 61000-4-3:2006+A1:2008+A2:2010
Fast Transients
EN 61000-4-4:2012
Surges
EN 61000-4-5:2014+A1:2017
Conducted Disturbances
EN 61000-4-6:2014
Magnetic Fields
EN 61000-4-8:2010
Voltage Dips and Interruptions
EN 61000-4-11:2004+A1:2017
Oscillatory Waves
EN 61000-4-12:2017
Emission Tests
Limits and Methods of Measurement of Electromagnetic Disturbance Characteristics of Industrial,Scientific and Medical(ISM) Radio-Frequency Equipment
EN 55011:2016
Electromagnetic Compatibility of Multimedia Equipment-Emission Requirements
EN 55032:2015
Limits for Harmonic Current Emissions for Equipment with Rated Current≤16A
EN 61000-3-2:2014
Limitation of Voltage Fluctuations and Flicker in Low-Voltage Supply Systems for Equipment with Rated Current≤16A
EN 61000-3-3:2013
Emission Standard for Industrial Environments
EN 61000-6-4:2007+A1:2011
Mechanical Tests
Spring Hammer Test
IEC 62052-11:2003
Vibration Test
IEC 62052-11:2003
Shock Test
IEC 62052-11:2003

Wiring Mode

Wiring Mode
Single Panel Mode I
Single Panel Mode I with One Mains Only (Wye)
Single Panel Mode I with One Mains Only (Delta)
Single Panel Mode I with Two Mains (Wye)
Single Panel Mode I with Two Mains (Delta)
Single Panel Mode II
Mains-I = Wye, Mains-II = Delta
Dual Panel Mode I
Mains-I/II = Wye, Optional Voltage-II = Delta Only
Dual Panel Mode II
Dual Panel Mode II (Mains-I/II = Wye)
Dual Panel Mode II (Mains-I/II = Delta)
Dual Panel Mode II (Mains-I/II = 1P3W Direct Connection)