PMC-592 Multi Circuit Power Monitor
Device Introduction |
|
Product Highlight |
|
Typical Application |
|
Related Products
Related Solutions
Specification
Technical Specification
Main Voltage Inputs(V1,V2,V3,VN)
Standard(Un)
277ULN/480ULL
Range
10% to 120% Un
PT Ratio
Mains I/II-Primary
Mains I/II-Secondary
Mains I/II-Primary
Mains I/II-Secondary
1-1,000,000V
1-480V
Overload
2xUn continuous,4xUn for 1s
Burden
<0.05VA@277ULN per phase
Frequency
45-65Hz
Mains Current Inputs
I Nominal(In)
5A/1A (CT rated Input)
Range
1% to 120%
Starting Current
0.3% of In
CT Ratio
6000 max.for 5A,30000max.for 1A
Overload
1.2xIn continuous,10xIn for 1s
Burden
<0.3 VA per phase
Power Supply for Main Unit(L+,N-)
Standard
95-277VAC/DC,±10%,47-440Hz
Burden
<6W
Branch Inputs
CT Ratio
400 Maximum
Burden
<0.05VA per phase
Starting Current
0.2% Imax
Solid-Core CT Strip
100A
5A
100A
5A
In=100A,Imax=100A,Range=0.2%-100%
In=5A,Imax=10A,Range=1%-100%
Split-Core CT
100A
200A
400A
800A
1600A
100A
200A
400A
800A
1600A
In=100A,Imax=120A,Range=5%-120%
In=200A,Imax=240A,Range=5%-120%
In=400A,Imax=480A,Range=5%-120%
In=800A,Imax=960A,Range=5%-120%
In=1.6kA,Imax=1.92kA,Range=5%-120%
Solid-Core CT
400A
800A
400A
800A
In=400A,Imax=480A,Range=5%-120%
In=800A,Imax=960A,Range=5%-120%
Digital Inputs(DI1,DI2,DIC)
Type
Dry contact,24VDC internally wetted
Sampling
1000Hz
Debounce
1-9999 ms programmable
Digital Outputs(DO11,DO12,DO21,DO22)
Type
Form A Mechanical Relay
Loading
5A@250VAC/30VDC
RTD Inputs(TC11,TC12,TC21,TC22)
Type
PT100
Range
-40°C-200°C
Environmental Conditions
Operating Temp.
-25 °C to + 70°C
Storage Temp.
-40 °C to + 85°C
Humidity
5% to 95% non-condensing
Atmospheric Pressure
70 kPa to 106 kPa
Pollution Degree
2
Overvoltage Category
CAT III
Mechanical Characteristics
Enclosure
Galvanized Steel
Unit Dimensions
260.5x154x55.5mm
IP Rating
IP50
Communications
Protocol
Modbus RTU,Modbus TCP,HTTP,SNMP,SNTP,SMTP
RS-485 Port(Standard)
2
Ethernet
1
Web Server
√
Features Summary
Display (Backlit)
Optional Color TFT 800×480 (Backlit)
Type of Measurement
ULN per Phase &Avg.
ULL per Phase&Avg.
Current per Phase &Avg.
Neutral Current (Meas.)
Frequency
kW per Phase & Total
kvar per Phase & Total
kVA per Phase& Total
PF per Phase& Total
kWh lmport/Export
kvarh Import/Export
kVAh Total
ULL per Phase&Avg.
Current per Phase &Avg.
Neutral Current (Meas.)
Frequency
kW per Phase & Total
kvar per Phase & Total
kVA per Phase& Total
PF per Phase& Total
kWh lmport/Export
kvarh Import/Export
kVAh Total
Power Quality
THD Voltage & Current
TOHD Voltage & Current
TEHD Voltage & Current
2nd-31st Harmonics
K-Factor
Voltage/Current Unbalance
TOHD Voltage & Current
TEHD Voltage & Current
2nd-31st Harmonics
K-Factor
Voltage/Current Unbalance
Battery-backed Real-time Clock
√
Demands
Present Demands and Max.Demands for This Month & Last Month
Alarm Setpoints
√
Logs
Max./Min.Log
This month & Last Month
Interval Energy Recorder
10000 entries
Data Recorder Log
10 Data Recorders
Max. Recording Depth @ 65535 records
Max. Recording Depth @ 65535 records
Waveform Recorder (WFR)
16 entries
SOE Log
1000 entries
On-board Log Memory
1GB
Accuracy
Parameters
Accuracy
Resolution
Mains Voltage
±0.2%
0.01V
Mains I1-I4
±0.2%
0.001A
kW,kVA
IEC 62053-22 Class 0.5S for Mains
IEC 62053-21 Class 1 for Branches
IEC 62053-21 Class 1 for Branches
0.001kX
kWh,kVAh
IEC 62053-22 Class 0.5S for Mains
IEC 62053-21 Class 1 for Branches
IEC 62053-21 Class 1 for Branches
0.1kXh
kvar,kvarh
IEC 62053-23 Class 2
0.01kvarh
0.1kvarh
0.1kvarh
PF
±1.0%
0.001
Frequency
±0.02Hz
0.01Hz
Harmonics
IEC 61000-4-7 Class B
0.01%
K-Factor
IEC 61000-4-7 Class B
0.01
RTD
±1.0°
0.1°
Standards of Compliance
Safety Requirements
LVD Directive 2014/35/EU
EN 61010-1: 2010
EN 61010-2-030: 2010
EN 61010-2-030: 2010
Electrical Safety in Low Voltage Distribution Systems up to 1000Vac and 1500Vdc
IEC 61557-12:2018(PMD)
Insulation
AC Voltage
Insulation Resistance
Impulse Voltage
AC Voltage
Insulation Resistance
Impulse Voltage
3.5kV @ 1 minute
>100MΩ
6kV+0%, 1.2/50µs
Electromagnetic Compatibility CE EMC Directive 2014/30/EU(EN 61326:2013)
Immunity Tests
Electrostatic Discharge
EN 61000-4-2:2009
Radiated Fields
EN 61000-4-3:2006+A1:2008+A2:2010
Fast Transients
EN 61000-4-4:2012
Surges
EN 61000-4-5:2014+A1:2017
Conducted Disturbances
EN 61000-4-6:2014
Magnetic Fields
EN 61000-4-8:2010
Voltage Dips and Interruptions
EN 61000-4-11:2004+A1:2017
Oscillatory Waves
EN 61000-4-12:2017
Emission Tests
Limits and Methods of Measurement of Electromagnetic Disturbance Characteristics of Industrial,Scientific and Medical(ISM) Radio-Frequency Equipment
EN 55011:2016
Electromagnetic Compatibility of Multimedia Equipment-Emission Requirements
EN 55032:2015
Limits for Harmonic Current Emissions for Equipment with Rated Current≤16A
EN 61000-3-2:2014
Limitation of Voltage Fluctuations and Flicker in Low-Voltage Supply Systems for Equipment with Rated Current≤16A
EN 61000-3-3:2013
Emission Standard for Industrial Environments
EN 61000-6-4:2007+A1:2011
Mechanical Tests
Spring Hammer Test
IEC 62052-11:2003
Vibration Test
IEC 62052-11:2003
Shock Test
IEC 62052-11:2003
Wiring Mode
Wiring Mode
Single Panel Mode I
Single Panel Mode I with One Mains Only (Wye)
Single Panel Mode I with One Mains Only (Delta)
Single Panel Mode I with Two Mains (Wye)
Single Panel Mode I with Two Mains (Delta)
Single Panel Mode I with One Mains Only (Delta)
Single Panel Mode I with Two Mains (Wye)
Single Panel Mode I with Two Mains (Delta)
Single Panel Mode II
Mains-I = Wye, Mains-II = Delta
Dual Panel Mode I
Mains-I/II = Wye, Optional Voltage-II = Delta Only
Dual Panel Mode II
Dual Panel Mode II (Mains-I/II = Wye)
Dual Panel Mode II (Mains-I/II = Delta)
Dual Panel Mode II (Mains-I/II = 1P3W Direct Connection)
Dual Panel Mode II (Mains-I/II = Delta)
Dual Panel Mode II (Mains-I/II = 1P3W Direct Connection)