PMC-1304-3 Communications Processor

SKU:
$900.00 USD

Sub-Model: PMC-1304-3-R-00-04-2-T2-XX-XXXX-E

PMC-1304-3-R-00-04-2-T2-XX-XXXX-E
PMC-1304-3-R-00-04-2-T2-XX-XXXX-E
PMC-1304-3-R-00-04-3-T2-XX-XXXX-E
PMC-1304-3-T-00-02-2-T2-XX-XXXX-E
PMC-1304-3-T-00-04-3-T2-XX-XXXX-E

Features:

  • Energy monitoring in building automation systems
  • Renewable energy and industrial monitoring
  • Ease of setup and integration
  • Biino hexibility

Main Documents

Description

PMC-1304-3 Communications Processor


Device Introduction

  • The PMC-1304-3 is the ideal embedded equipment for connecting RS-422 or RS-485 enabled serial devices to an IP-based LAN, making it possible for SCADA or other applications to access serial devices over a LAN for monitoring and control applications.
  • The PMC-1304-3 has been specifically designed with industrial automation in mind and therefore provides un-surpassed performance and reliability under the harshest industrial environments. The basic Model, PMC-1304-3-T, provides Modbus Gateway function from Modbus TCP to RTU and supports interrogation from multiple Modbus Masters. The optional RTU Model, PMC-1304-3-R, provides Modbus Mastering capability with local data caching and logging to enhance overall system performance and redundancy. Not only does the RTU Model support the polling of Real-Time data, it also supports the uploading of Data Logs, Event Logs and Waveform Logs for CET devices that provide these advanced capabilities

Product Highlight

  • Communications Processor for Connecting Serial Devices to an IP‐based LAN
  • 35mm DIN Rail (115x63x145mm)
  • LED Indicators
  • Basic Model Provides Modbus Gateway Function from Modbus TCP to RTU
  • RTU Model Provides Modbus Mastering Capability with Local Data Caching and Logging.
  • Automatic Data Log push to external FTP Server
  • 2xRS-485, Option for Two Additional RS-485

Typical Application

Related Products

Related Solutions

Specification

Technical Specification

10/100 Base Ethernet Port (P1,P2)
Standard
10/100BaseT, RJ45 connector
Cable
CAT5, CAT5e (100m maximum)
Serial Ports (P3,P4,P5,P6)
Standard
1xRS-422/485 (P3), 3xRS-485 (P4,P5,P6)
Comm. Parameters:
  Data bits
  Stop bits
  Parity
  Baud rate

5,6,7,8
1,2
None,Even,Odd,Mark,Space br
300 to 115,200 bps
LED Indicators
Run (Green):
  On
  Blinking
  Off

Abnormal condition
Working normally
Not powered up or abnormal condition
Alarm (Red):
  On
  Blinking

Abnormal condition
Restoring default parameters
P1&P2 (Yellow):
  On
  Blinking
  Off

Connected but no data activities
Data activities
Disconnected
P3&P4&P5&P6:
  Rx(Green) Blinking
  Tx(Yellow) Blinking

Receiving data
Transmitting data
Protocol
Protocol
ModbusRTU, ModbusTCP, FTP, HTTP
Power Supply(L+,N-)
Standard
95-250VAC/DC, 47-440Hz
Optional
20-60VDC Single Power Supply
20-60VDC Dual Power Supply
Burden
<5W
Protection
ESD Protection
15kV (Contactless) and 6kV (Contact) ESD protection for all serial signals
Isolation Protection
3kV for all Serial signals
1.5 kV for Ethernet Ports
Environmental Conditions
Operating Temp.
-25 °C to + 70°C
Storage Temp.
-40 °C to + 85°C
Humidity
5% to 95% non-condensing
Atmospheric Pressure
70 kPa to 106 kPa
Mechanical Characteristics
Casing
Galvanized Iron
Unit Dimensions
115x63x145mm
Shipping Weight
0.95kg
Shipping Dimensions
300x210x150mm
Mounting
DIN-Rail or Surface Mounting
IP Rating
IP30

Standards of Compliance

Safety Requirements
Insulation
IEC 60255-5-2000
Dielectric Test
2kV @ 1 minute
Insulation Resistance
>100MΩ
Impulse Voltage
5kV
Electromagnetic Compatibility
Electrostatic Discharge
IEC 61000-4-2:2001 Level IV
Radiated Fields
IEC 61000-4-3:2006 Level III
Fast Transients
IEC 61000-4-4:2004 Level IV
Surges
IEC 61000-4-5:2005 Level IV
Conducted Disturbances
IEC 61000-4-6:2006 Level III
Magnetic Fields
IEC 61000-4-8:2001 Class III
Oscillatory waves
IEC 61000-4-12:1995 Level III