Main Documents
Description
PMC-D721MD DC Multifunction Meter
Device Introduction |
|
Product Highlight |
|
Typical Application |
|
Related Products
Related Solutions
Specification
Technical Specification
DC Inputs
Voltage Input
Standard(Un)
Measurement Range
Starting Voltage
Overload
Standard(Un)
Measurement Range
Starting Voltage
Overload
1000V DC
1% to 120% Un
10V DC
1.2xUn continuous, 2xUn for 1s
Current Input
Nominal Input(In)
Measurement Range
Starting Current
Max.Shunt Current
Overload
Nominal Input(In)
Measurement Range
Starting Current
Max.Shunt Current
Overload
100mV DC (via Shunt Output), configurable for Shunts rated at 50,60,75 and 100mV
1% to 120% In
0.2% of In
10,000A
1.2xIn continuous, 10xIn for 10s, 20xIn for 1s
Power Supply(L+,N-)
Standard
95-250VAC/DC,±10%,47-440Hz
Burden
<2W
Digital Inputs(DI1,DI2,DIC)
Type
Dry contact,24VDC internally wetted
Hysteresis
20ms minimum
Pulse Outputs(DO11,DO12,DO21,DO22)
Type
Front Panel LED / Solid State DO
Pulse Constant
25 /100 /400 /1000 /3200 Imp/kWh
Pulse Width
80ms±20ms
Communications
RS-485 Port
1
Protocol
Modbus RTU
Baud Rate
1200 /2400 /4800 /9600 /19200 bps
Environmental Conditions
Operating Temp.
-25 °C to + 70°C
Storage Temp.
-40 °C to + 85°C
Humidity
5% to 95% non-condensing
Atmospheric Pressure
70 kPa to 106 kPa
Mechanical Characteristics
Panel Cutout
68x68 mm
Unit Dimensions
72x72x71.8 mm
IP Rating
IP52
Shipping Weight
0.34kg
Shipping Dimensions
125x110x80mm
Features Summary
Display (Backlit)
B&W(Backlit)
Type of Measurement
Voltage
Current
Active Power
kWh lmport/Export
Current
Active Power
kWh lmport/Export
Logs
SOE Log
32 entries
Accuracy
Parameters
Accuracy
Resolution
Voltage
±0.2%
0.1V
Current
±0.2%
0.01A
kW
±0.5%
0.001kW
kWh
Class 0.5
0.1kWh
Standards of Compliance
Safety Requirements
CE LVD 2014/35/EU
EN 61010-1: 2010
EN 61010-2-030: 2010
EN 61010-2-030: 2010
Electrical Safety in Low Voltage Distribution Systems up to 1000Vac and 1500Vdc
IEC 61557-12:2018(PMD)
Insulation
Dielectric test:
Insulation Resistance:
Impulse Voltage:
Dielectric test:
Insulation Resistance:
Impulse Voltage:
IEC 62052-11: 2003
IEC 62053-21: 2003
4kV@1 minute
>40MΩ
6kV,1.2/50µs
IEC 62053-21: 2003
4kV@1 minute
>40MΩ
6kV,1.2/50µs
Electromagnetic Compatibility CE EMC Directive 2014/30/EU(EN 61326:2013)
Immunity Tests
Electrostatic Discharge
EN 61000-4-2:2009
Radiated Fields
EN 61000-4-3:2006+A1:2008+A2:2010
Fast Transients
EN 61000-4-4:2012
Surges
EN 61000-4-5:2014+A1:2017
Conducted Disturbances
EN 61000-4-6:2014
Magnetic Fields
EN 61000-4-8:2010
Voltage Dips and Interruptions
EN 61000-4-11:2004+A1:2017
Ring Waves
EN 61000-4-12:2017
Emission Tests
Limits and Methods of Measurement of Electromagnetic Disturbance Characteristics of Industrial,Scientific and Medical(ISM) Radio-Frequency Equipment
EN 55011:2016
Electromagnetic Compatibility of Multimedia Equipment - Emission Requirements
EN 55032:2015
Limits for Harmonic Current Emissions for Equipment with Rated Current≤16A
EN 61000-3-2:2014
Limitation of Voltage Fluctuations and Flicker in Low-Voltage Supply Systems for Equipment with Rated Current≤16A
EN 61000-3-3:2013
Emission Standard for Industrial Environments
EN 61000-6-4:2007+A1:2011
Mechanical Tests
Spring Hammer Test
IEC 62052-11:2003
Shock Test
IEC 62052-11:2003
Vibration Test
IEC 62052-11:2003
- Choosing a selection results in a full page refresh.