PMC-D721MD DC Multifunction Meter

SKU:
$120.00 USD

Sub-Model: PMC-D721MD-L112AAE

PMC-D721MD-L112AAE
PMC-D721MD-L112AAE

Main Documents

Description

PMC-D721MD DC Multifunction Meter


Device Introduction

  • The PMC-D721MD DC Multifunction Meter is CET’s latest offer for the low-cost DC metering market. Housed in an industry standard DIN form factor measuring 72x72x71.8mm, it is perfectly suited for industrial, commercial and utility DC metering applications.
  • The PMC-D721MD complies with Class 0.5 kWh Accuracy Standard and features quality construction, multifunction measurements and a bright, easy to read LCD display. The PMC-D721MD comes standard with two Front Panel LED indicators for Energy Pulsing and Communication. It provides two Digital Inputs for status monitoring and two Solid State Pulse Outputs for kWh Energy Pulsing applications. The standard SOE Log records meter events such as power-off, setup changes and DI operations in 1ms resolution. With a standard RS-485 port and Modbus protocol support, the PMC-D721MD becomes a vital component of an intelligent, multifunction monitoring solution for any DC Power and Energy Management systems.

Product Highlight

  • Low-Cost DC Multifunction Meter
  • Class 0.5 kWh Compliant
  • DIN72 (68x68mm Cutout)
  • Backlit B&W LCD Display
  • DC V&I, kW and Event Log
  • Modbus RTU
  • 1xRS-485
  • 2xDI, 2xSS Pulse Output

Typical Application

  • DC Inverter, DC Panel Metering and DC Charging Station
  • Industrial and commercial DC metering
  • DC Distribution Monitoring

Related Products

Related Solutions

Specification

Technical Specification

DC Inputs
Voltage Input
   Standard(Un)
   Measurement Range
   Starting Voltage
   Overload

1000V DC
1% to 120% Un
10V DC
1.2xUn continuous, 2xUn for 1s
Current Input
  Nominal Input(In)

  Measurement Range
  Starting Current
  Max.Shunt Current
  Overload

100mV DC (via Shunt Output), configurable for Shunts rated at 50,60,75 and 100mV
1% to 120% In
0.2% of In
10,000A
1.2xIn continuous, 10xIn for 10s, 20xIn for 1s
Power Supply(L+,N-)
Standard
95-250VAC/DC,±10%,47-440Hz
Burden
<2W
Digital Inputs(DI1,DI2,DIC)
Type
Dry contact,24VDC internally wetted
Hysteresis
20ms minimum
Pulse Outputs(DO11,DO12,DO21,DO22)
Type
Front Panel LED / Solid State DO
Pulse Constant
25 /100 /400 /1000 /3200 Imp/kWh
Pulse Width
80ms±20ms
Communications
RS-485 Port
1
Protocol
Modbus RTU
Baud Rate
1200 /2400 /4800 /9600 /19200 bps
Environmental Conditions
Operating Temp.
-25 °C to + 70°C
Storage Temp.
-40 °C to + 85°C
Humidity
5% to 95% non-condensing
Atmospheric Pressure
70 kPa to 106 kPa
Mechanical Characteristics
Panel Cutout
68x68 mm
Unit Dimensions
72x72x71.8 mm
IP Rating
IP52
Shipping Weight
0.34kg
Shipping Dimensions
125x110x80mm
Features Summary
Display (Backlit)
B&W(Backlit)
Type of Measurement
Voltage
Current
Active Power
kWh lmport/Export
Logs
SOE Log
32 entries

Accuracy

Parameters
Accuracy
Resolution
Voltage
±0.2%
0.1V
Current
±0.2%
0.01A
kW
±0.5%
0.001kW
kWh
Class 0.5
0.1kWh

Standards of Compliance

Safety Requirements
CE LVD 2014/35/EU
EN 61010-1: 2010
EN 61010-2-030: 2010
Electrical Safety in Low Voltage Distribution Systems up to 1000Vac and 1500Vdc
IEC 61557-12:2018(PMD)
Insulation

Dielectric test:
Insulation Resistance:
Impulse Voltage:
IEC 62052-11: 2003
IEC 62053-21: 2003
4kV@1 minute
>40MΩ
6kV,1.2/50µs
Electromagnetic Compatibility CE EMC Directive 2014/30/EU(EN 61326:2013)
Immunity Tests
Electrostatic Discharge
EN 61000-4-2:2009
Radiated Fields
EN 61000-4-3:2006+A1:2008+A2:2010
Fast Transients
EN 61000-4-4:2012
Surges
EN 61000-4-5:2014+A1:2017
Conducted Disturbances
EN 61000-4-6:2014
Magnetic Fields
EN 61000-4-8:2010
Voltage Dips and Interruptions
EN 61000-4-11:2004+A1:2017
Ring Waves
EN 61000-4-12:2017
Emission Tests
Limits and Methods of Measurement of Electromagnetic Disturbance Characteristics of Industrial,Scientific and Medical(ISM) Radio-Frequency Equipment
EN 55011:2016
Electromagnetic Compatibility of Multimedia Equipment - Emission Requirements
EN 55032:2015
Limits for Harmonic Current Emissions for Equipment with Rated Current≤16A
EN 61000-3-2:2014
Limitation of Voltage Fluctuations and Flicker in Low-Voltage Supply Systems for Equipment with Rated Current≤16A
EN 61000-3-3:2013
Emission Standard for Industrial Environments
EN 61000-6-4:2007+A1:2011
Mechanical Tests
Spring Hammer Test
IEC 62052-11:2003
Shock Test
IEC 62052-11:2003
Vibration Test
IEC 62052-11:2003