iMeter 8 Advanced Power Quality Analyzer
Product Overview |
|
Product Highlight |
|
Typical Application |
|
Related Products
Related Solutions
Specification
Technical Specification
VoltageInputs(V1,V2,V3,VN,V4,V4N)
Standard Un
400VLN/690VLL+20%
Range
1% to 200% Un for 400ULN nominal
Overload
2xUn continuous,4xUn for 1s
Burden
<0.5VA/per phase
PT Ratio
Primary
Secondary
V4 Primary
V4 Secondary
Primary
Secondary
V4 Primary
V4 Secondary
1 to 1,000,000
1 to 1,500
1 to 1,000,000
1 to 1,500
Measurement Category
CAT III 1000V
Frequency
40Hz-60Hz@50Hz,48Hz-72Hz@60Hz
Current Inputs(I11,I12,I21,I22,I31,I32,I41,I42,I51,I52)
Standard(In)
5A(Standard),1A(Optional)
Range
1% to 400% In
Starting Current
0.1% In
Overload
4xIn continuous, 20xIn for 1s
Burden
<0.5VA/per phase @ 5A
<0.1VA/per phase @ 1A
<0.1VA/per phase @ 1A
Optional SCCP Options
SCCP-50A-500mV
SCCP-200A-200mV
SCCP-500A-500mV
SCCP-5000-500mV
SCCP-50A-500mV
SCCP-200A-200mV
SCCP-500A-500mV
SCCP-5000-500mV
5A/50A (In/Imax), max. 500mV Output
20A/200A (In/Imax), max. 200mV Output
500A Imax, max. 500mV Output
Selectable 500A/5000A (Imax) Rogowski Coil, max. 500mV Output
CT Ratio
Primary
Secondary
I4 Primary
I4 Secondary
Primary
Secondary
I4 Primary
I4 Secondary
1 to 30,000
1 to 50
1 to 30,000
1 to 50
Power Supply(L+,N-)
Standard
95-250VAC/VDC ± 10%, 47-440 Hz
Optional
20-60VDC
Burden
< 12W
Overvoltage Category
OVC III 300V
Digital Inputs (DIC,DI1 to DI8 or DI16)
Type
Dry contact,24VDC internally wetted
Optional
110V/220V AC/DC externally wetted
Sampling
1000Hz
Hysteresis
1ms minimum
Form A Relay Outputs (DO1 to DO3 or optional DO1 to DO7)
Type
Form A Mechanical Relay
Loading
5A@250VAC or 30VDC
Form C Relay Outputs (Alarm 1, 2, 3)
Type
Form C Mechanical Relay
Loading
8A @ 250VAC or 24VDC
Pulse Outputs (E1+,E1-,E2+,E2-,E3+,E3-,E4+,E4-)
Type
Form A Solid State Relay
Isolation
Optical
Max.Load Voltage
30VDC
Max.Forward Current
4mA
Optional Analog Inputs(AI1+,AI1-,AI2+,AI2-)
Type
0-20/4-20mADC
Overload
24mA maximum
Optional Analog Outputs(AO1+,AO1-,AO2+,AO2-)
Type
0-20/4-20mA
Loading
500Ω maximum
Overload
24mA maximum
Environmental Conditions
Operating Temp.
-25 °C to + 70°C
Storage Temp.
-40 °C to + 85°C
Humidity
5% to 95% non-condensing
Atmospheric Pressure
63 kPa to 110 kPa
Pollution Degree
2
Mechanical Characteristics
Panel Cutout
186x186mm
Unit Dimensions
192x192x182.4mm
IP Rating
IP52
Communications
Protocol
Modbus RTU, Modbus TCP ,HTTPS, SNTP, SMTPS, FTP, Ethernet Gateway, IEC61850, IEEE1588(PTP)
RS-485 Port
2
Ethernet
2
Web Server
√
Features Summary
Display (Backlit)
Color TFT 800x480(Backlit)
Type of Measurement
ULN per Phase &Avg.
ULL per Phase&Avg.
Current per Phase &Avg.
Neutral Current (Meas./Calc.)
Frequency
kW per Phase & Total
kvar per Phase & Total
kVA per Phase& Total
PF per Phase& Total
kWh lmport/Export
kvarh Import/Export
kVAh Total
ULL per Phase&Avg.
Current per Phase &Avg.
Neutral Current (Meas./Calc.)
Frequency
kW per Phase & Total
kvar per Phase & Total
kVA per Phase& Total
PF per Phase& Total
kWh lmport/Export
kvarh Import/Export
kVAh Total
Power Quality
THD Voltage & Current
TOHD Voltage & Current
TEHD Voltage & Current
2nd-63rd Harmonics
K-Factor
Voltage/Current Unbalance
Dip Swell Detection
Transient Detection
2-150kHz Conducted Emission
TOHD Voltage & Current
TEHD Voltage & Current
2nd-63rd Harmonics
K-Factor
Voltage/Current Unbalance
Dip Swell Detection
Transient Detection
2-150kHz Conducted Emission
Time Synchronization
RTC,IEEE 1588(PTP),SNTP, Modbus RTU/TCP,GPS(Optional),IRIG-B(Optional)
Demands
Present and Predicted Demands
Max.Demands for This Month & Last Month
Max./Min. values per Demand Interval
Demand synchronization with DI
Max.Demands for This Month & Last Month
Max./Min. values per Demand Interval
Demand synchronization with DI
Multi-Tariff TOU capability
Two TOU schedules, each providing:
12 Seasons
90 Holidays
20 Daily Profiles, each with 12 Periods in 15-minute interval
8 Tariffs
12 Seasons
90 Holidays
20 Daily Profiles, each with 12 Periods in 15-minute interval
8 Tariffs
Setpoints
256 standard and 16 High-Speed Setpoints
Logs
Max./Min.Log
4 Recorders
Interval Energy Recorder
65535 entries
Accumulative Energy Recorder
65535 entries
Data Recorder
8 DR Logs
Statistical Data Recorder (SDR)
16 SDR Logs
30 days @ 1-minute, 300 days @ 10-minute, 450-day @ 15-minute
30 days @ 1-minute, 300 days @ 10-minute, 450-day @ 15-minute
Waveform Recorder
128 entries
Disturbance Waveform Recorder
128 entries
RMS Recorder
128 entries
Pst Log
56520 entries (i.e. 1-year: 365x24x6)
Plt Log
4380 entries (i.e. 1-year: 365x12)
SOE Log
1024 entries
Device Log
1024 entries
Audit Logs
2048 entries
On-board Log Memory
8GB
Accuracy
Parameters
Accuracy
Resolution
Voltage
±0.1%
0.001V
I1,I2,I3
±0.1%
SCCPA Option: ±0.1% + Error of SCCP
SCCPA Option: ±0.1% + Error of SCCP
0.001A
I4
±0.1%
0.001A
I5
±0.5%
0.001A
P,Q,S
±0.2%
SCCPA Option: ±0.5%
SCCPA Option: ±0.5%
0.001kX
kWh,kVAh
IEC 62053-22 Class 0.2S
SCCPA Option: IEC 62053-21 Class 1
SCCPA Option: IEC 62053-21 Class 1
0.1kXh
kvarh
IEC 62053-24 Class 0.5S
IEC 62053-23 Class 2
SCCT/SCCTA:IEC 62053-24 Class 1
SCCPA Option: IEC 62053-24 Class 1
IEC 62053-23 Class 2
SCCT/SCCTA:IEC 62053-24 Class 1
SCCPA Option: IEC 62053-24 Class 1
0.1kvarh
PF
±0.2%
SCCPA Option:±0.5%
SCCPA Option:±0.5%
0.001
Frequency
±0.003 Hz
0.001Hz
Harmonics
IEC 61000-4-7 Class I
0.001
Phase Angle
±0.2°
SCCPA Option:±0.2°+Phase Error of SCCP
SCCPA Option:±0.2°+Phase Error of SCCP
0.1°
U Unbalance
±0.1%
0.01%
I Unbalance
±0.5%
0.01%
Pst,Plt
IEC 61000-4-15 Class F1
0.01%
Standards of Compliance
Safety Requirements
CE LVD 2014/35/EU
EN 61010-1: 2010
EN 61010-2-030: 2010
EN 61010-2-030: 2010
Electrical Safety in Low Voltage Distribution Systems up to 1000Vac and 1500Vdc
IEC 61557-12:2018(PMD)
Insulation
AC Voltage: 2kV@1 minute
Insulation Resistance: >100MΩ
Impulse Voltage: 6kV,1.2/50µs
AC Voltage: 2kV@1 minute
Insulation Resistance: >100MΩ
Impulse Voltage: 6kV,1.2/50µs
IEC 62052-11: 2003
IEC 62053-22: 2003
EN 61010-1: 2010
IEC 62053-22: 2003
EN 61010-1: 2010
Electromagnetic Compatibility CE EMC Directive 2014/30/EU(EN 61326:2013)
Immunity(EN50082-2)
Electrostatic Discharge
EN 61000-4-2:2009
Radiated Fields
EN 61000-4-3:2006+A1:2008+A2:2010
Fast Transients
EN 61000-4-4:2012
Surges
EN 61000-4-5:2014+A1:2017
Conducted Disturbances
EN 61000-4-6:2014
Magnetic Fields
EN 61000-4-8:2010
Voltage Dips and Interruptions
EN 61000-4-11:2004+A1:2017
Ring Waves
EN 61000-4-12:2017
Emission Tests
Limits and Methods of Measurement of Electromagnetic Disturbance Characteristics of Industrial,Scientific and Medical(ISM) Radio-Frequency Equipment
EN 55011:2016
Limits and Methods of Measurement of Radio Disturbance Characteristics of Information Technology Equipment
EN 55032:2015
Limits for Harmonic Current Emissions for Equipment with Rated Current≤16A
EN 61000-3-2:2014
Limitation of Voltage Fluctuations and Flicker in Low-Voltage Supply Systems for Equipment with Rated Current≤16A
EN 61000-3-3:2013
Emission Standard for Industrial Environments
EN 61000-6-4:2007+A1:2011
Mechanical Tests
Vibration Test(Response/Endurance)
IEC 255-2-1: 1989
Shock Test(Response/Endurance)
IEC 255-2-2
Bump Test
IEC 255-2-2
Power Quality
Voltage Characteristics of Electricity supplied by Public Distribution Systems
EN 50160: 2010
General Guide on Harmonic and Interharmonic Measurements and Instrumentation, for Power Supply Systems and Equipment Connected Thereto
IEC 61000-4-7: 2009
Flickermeter - Functional and Design Specifications
IEC 61000-4-15: 2010
Testing and Measurement Techniques-Power Quality Measurement Methods
IEC 61000-4-30: 2021 Ed. 3.1 Class A Certified
Power Quality Measurement in Power Supply Systems-Part2: Functional Test and Uncertainty Requirements
IEC 62586-2: 2021 Ed.2.1
Harmonic Control in Electrical Power Systems
IEEE Std 519-2022
Wiring Mode
Wiring Mode
3P4W
3-Phase 4-Wire Wye with 3PTs and 4CTs
3P3W
3-Phase 3-wire Direct Delta Direct Connection with 3CTs
- Choosing a selection results in a full page refresh.